Reasons for the abnormal contact of the AC contactor and its treatment:

The AC contactor is not properly connected, which means that the AC contactor is too slow to pull, the contact cannot be completely closed, and the iron core emits abnormal noise and other abnormal phenomena. The reasons for the abnormal contact of the AC contactor and the treatment methods are as follows:

1. Since the power supply voltage of the control circuit is lower than 85% of the rated voltage, the electromagnetic force generated after the electromagnetic coil is energized is small, and the movable iron core cannot be quickly sucked toward the static iron core, causing the contactor to suck slowly or the suction is not tight. The power supply voltage of the control loop should be adjusted to the rated operating voltage.

2. The spring pressure is insufficient, causing the contactor to be improperly sucked; the reaction force of the spring is too large, causing the suction to be slow; the contact spring pressure overshoot is too large, so that the iron core cannot be completely closed; the spring pressure and release pressure of the contact Too large, causing the contacts to not close completely. The solution is to properly adjust the spring pressure and replace the spring if necessary.

3. Because the gap between the moving and static iron core is too large, the movable part is stuck, the rotating shaft is rusted or deformed, and the contactor is not properly sucked. During the treatment, the moving iron core can be removed for inspection, the gap is adjusted, the shaft and the support rod are cleaned, and the fittings are replaced if necessary.

4. Due to long-term frequent collisions, the iron core surface is not flat and expands outward along the thickness of the laminated sheet. At this time, the boring tool can be used for trimming and the iron core can be replaced if necessary.

5. The short-circuit ring breaks, causing the core to make an abnormal sound. In this case, replace the short-circuit ring of the same size.